Room Tone Register

The 4.5 dB gap came from weighting and time constant, not from a broken meter; both readings were correct and neither was the room's floor as anyone would record in it.

Two sound meters, one room, 4.5 dB apart

written 2026-08-11responsible Room Tone Register (a named register, not a person)

< 30 dB(A) anything 30 – 40 voice, dialogue 40 – 50 loud sources only 50 + dB(A) change rooms FLOOR BAND permitted work closes when the compressor starts. measure both states
Four bands. The band decides the work, not the room's appearance. Not to scale.

The two readings

MeterWeightingTime constantReading
Meter 1ASlow36.2 dB
Meter 2AFast40.7 dB
Meter 1CSlow43.9 dB
Meter 2CSlow44.1 dB

The fourth row is the interesting one. With both meters set to C and slow, they agree within 0.2 dB. That single comparison rules out a calibration fault and rules out a hardware fault, and it takes about forty seconds to run. Do it first, before you suspect either instrument.

Three causes, and how to tell them apart

  1. Time constant. Fast averaging follows the peak of a fluctuating source and reads high. Switch both to slow and re-read.
  2. Weighting. A and C differ most where low-frequency energy lives. Switch both to the same weighting and re-read.
  3. Position. Two metres apart in the same room can differ by 3 dB near a boundary, because the reflected energy adds to the direct. Swap the meters' positions and re-read; if the numbers swap, it was position.

What the register does with this

It reports the weighting, the time constant and the position alongside every floor figure. A number without those three is not evidence, and the 4.5 dB gap in this note is what happens when two people each hold a defensible number and neither states the conditions. This is also the reason the register treats a single quoted figure in a manufacturer's room claim with scepticism.

A phone app can be useful here precisely because it is a third instrument. If a phone, a cheap meter and an expensive meter all agree on the relative difference between two rooms, the relative comparison is sound even when none of the absolute numbers is.

Source log

  1. 01Noise at work: advice for employers (UK HSE INDG362)supports the measurement practice that requires a stated weighting and averaging
  2. 02The Control of Noise at Work Regulations (UK HSE)supports the regulatory requirement that measurements be made to a defined method
  3. 03Deafness and hearing loss (WHO fact sheet)supports the public-health framing of why an unstated measurement is not usable

Each line points at one specific document. No line is a home page.

Leave this page Close this page once both meters are on the same settings. The disagreement is then a position problem or it is gone.